Combustible Gas Detector, Controller and Transducer
User Instructions
IMPORTANT: Keep these User Instructions for reference.
GD-6
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - User Instructions

3Macurco™ Combustible Gas Detector, Controller and Transducer User Instructions IMPORTANT: Keep these User Instructions for reference.GD-6

Page 2

16 17Operation Test1. Remove the single screw in the middle of the front cover of the 3M™ Macurco™ GD-6 Combustible Gas Detector.2. Remove the front

Page 3

18 19Gas TestingTesting the Fan RelayNote: The gas concentration to activate the fan relay depends on the setting.1. Remove the Philips screw on the

Page 4

20 215. The 4-20mA output should ramp up from 4mA in clean air to 20mA at 50% LEL. See 4-20mA diagram in these User Instructions.Note: If the 4-20mA

Page 5 - Modular Connectors

22 237. Press the Enter button and the display will read 10 alternating with the gas, mE, Pro or Hy (blinking), indicating the sensor is looking for

Page 7

3M Occupational Health and Environmental Safety Division3M Center, Building 0235-02-W-70St. Paul, MN 55144-1000Printed in U.S.A.© 3M 2008-2011. All r

Page 8

Requester: Farrel AllenCreator: deZinniaFile Name: 34870758629.inddStructure #: SS-41964Date: 6/17/11Printed Colors – Front:Printed Colors – Ba

Page 9

1TABLE OF CONTENTSGENERAL SAFETY INFORMATION ...

Page 10 - W WARNING

2 3W WARNINGGENERAL SAFETY INFORMATIONIntended UseThe 3M™ Macurco™ GD-6 Combustible Gas Detector, Controller and Transducer is a low voltage device wi

Page 11

4 5Ifyouhaveanydoubtsabouttheapplicabilityoftheequipmenttoyourjobsituation,consultanIndustrialHygienistorcall3MMacurco Technical

Page 12

6 7Installation1. The 3M™ Macurco™ GD-6 Combustible Gas Detector mounts on a type 4S electrical box supplied by the contractor. 2. Connect the 3M™ M

Page 13

8 9Typical Multiple 3M™ Macurco™ GD-6 Combustible Gas Detector InstallationINSTALLATION NOTES1. One sensor per 900 square feet (approximately).2. If

Page 14

10 11GD-6Main Fan Power120VAC ALARM120VAC PowerExhaust Fanscoilcoilpower outputGD-6– +power output– +8 7 6 5 443322111 13 3 4 5 6 7 8 9224 V RETN.C.N.

Page 15

12 13To change settings, remove the Philips screw on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector. Pull off the front cover of the unit

Page 16 - Match Colors:

14 15Selecting Fan Minimum Run Time – “Frr”To select the Fan Minimum Runtime setting, in normal mode, press the Next button twice to get to “Con” or t